1. The desulfurizer should be iron oxide, and the space velocity of desulfurizer should be 200 H-1 ~ 400 H-1;
2 .沼氣初次通過脫硫劑每米床層時的壓力降應小于100Pa;
2. The pressure drop of biogas passing through the desulfurizer bed for the first time should be less than 100Pa;
3 .每層顆粒狀脫硫劑裝填高度宜為1.0m~1.4m;
3. The filling height of each layer of granular desulfurizer should be 1.0m ~ 1.4m;
4 .沼氣通過顆粒狀脫硫劑的線速度宜為0.020m/s~0.025m/s;
4. The linear velocity of biogas passing through granular desulfurizer should be 0.020m/s ~ 0.025m/s;
5 .脫硫塔的操作溫度應為25℃~35℃,寒冷地區(qū)的脫硫設施應有保溫或采暖措施;
5. The operating temperature of desulfurization tower should be 25 ℃ ~ 35 ℃. Thermal insulation or heating measures should be taken for desulfurization facilities in cold areas;
6 .脫硫塔底部的低處應設置排污閥;
6. Blowdown valve should be set at the bottom of desulfurization tower;
7 .每臺脫硫裝置應有獨立的放散管;
7. Each desulfurization unit shall have an independent vent pipe;
8 .脫硫劑在塔內再生時應設置進空氣管,在線再生時,宜配備在線氧監(jiān)控系統。
8. When the desulfurizer is regenerated in the tower, the air inlet pipe should be set. When the desulfurizer is regenerated online, the online oxygen monitoring system should be equipped.